Plan Number: T17PI00013
Parcel: Unknown

Address:
2850 E DREXEL RD

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T17PI00013
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2017 GARY WITTWER DOT LANDSCAPE REVIEW Denied There appears to be 3 or 4 trees in the ROW that are labeled PIP on the NPPO Plan, but they are not shown on the landscape plans. Please include them.
03/09/2017 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved
03/14/2017 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Denied
03/14/2017 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
03/15/2017 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change March 13, 2017


SUBJECT: Dock-Hi Industrial Drexel Rd Improvements, I-2017-002 - T17PI00008

PROJECT REVIEWER: Richard Leigh, TDOT Engineering Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to final approval. Please include a response letter addressing the following comments and return any redlined drawings with subsequent submittal.

1. Sheet 1: Include the plan number "I-2017-002" in the title block of each sheet.

2. Sheet 1: Include the PIA activity number "T17PI00013" on cover sheet.

3. Include Development Plan Number on cover Sheet.

4. Sheet 1: Include the projects administrative address on cover sheet.

5. The City of Tucson has adopted the Pima Associates of Government (PAG) 2015 Standard Specification for Public Improvements (SSPI) and Standard Details (SD). Please revise plan set to reflect this change.

6. Sheet 1: Use title block with signature place holders for cover sheet.

7. Sheet 2: Indicate the placement of a curb terminal end treatment at end of curb return at Sta. 23+69.24, 23 RT (Drexel Rd.).

8. Sheet 2 through 4: Verify that all section callouts reference correct page, revises accordingly.

9. Provide a pavement terminal detail for the pavement tapper ends.

10. A public drainage and maintenance easements will be required for the culvers and headwall structures that encroach onto private property per Section 3.4 ofthe City Drainage Manual. Additionally, a flowage easement will be required for the channel and culverts, on private property, that run parallel along Drexel Road City Drainage Manual Sec. 3.4.

11. Provide details for the proposed modified headwalls and wing walls.

12. Please Refer to redline drawings for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.
03/15/2017 LPETERS2 DOT PERMITS & CODES REVIEW Denied I have reviewed this plan and have the following comments:

1. Note 5 calls out the 2003 Standard and Details. We have gone to the 2015 PAG standards and Details

2. Providing 4 - 38" x 60" HERCP will span 20 feet and meet the requirements to be included in the National Bridge Inventory. We will need to provide electronic copies of the plans and a structure number application to ADOT.

3. Sheet 8 - Detail B - This detail shows 6-inch thick concrete sidewalk per sTD Detail 200. Typically sidewalk is only 4 inches thick unless it is subject to vehicular traffic.

4. Sheet 8 - A note at the northwest outlet of these pipe has mentioned City forces to re-establish the channel to the north and west. Has this been discussed with our Streets Maintenance Section? Is this a public drainageway?

No further comments.

Lance Peterson, P.E.
(520) 837-6777
03/20/2017 JIM FEMLING DOT STREET MAINTENANCE REVIEW Passed No comments from JFemling - Approved per LPeterson 03/20/17 - LI
03/20/2017 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
03/20/2017 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed