Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17OT00465
Parcel: 12215277A

Address:
3309 E SENECA ST

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - FLOODPLAIN

Permit Number - T17OT00465
Review Name: PLANS OK TO SUBMIT - FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2017 PAUL BAUGHMAN ENGINEERING REVIEW Approved May 3, 2017
FLOODPLAIN USE PERMIT NO.: T17OT00465
ADDRESS: 3309 E Seneca Street Tucson, Arizona 85716
OWNER: Gregory Rupp
3309 E Seneca St, Tucson Arizona 85716

The applicant is authorized to use a portion of the City of Tucson Flood Hazard Area per the City of Tucson Flood Hazard Area delineation of the Christmas Avenue Wash, specifically described as:

A portion of Parcel 122-15-277A; Verde Amended S200.5' W79.8' E242.8' Lot 12 BLK 1

For the purpose of constructing an elevated Single Family Residential Home and shop and detached studio.

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit.

This floodplain use permit is issued with the following 9 conditions:

1) This permit becomes invalid and is subject to additional floodplain review, if any required development changes the demolishing of the buildings, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from demolishing the commercial building within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson.

2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

3) For purposes of this permit the following flood elevations shall be used for the shop, studio and single family home:
Base Flood Elevation (BFE) = 2440.28 feet NAVD 1988
Regulatory Flood Elevation (RFE) = 2441.28 feet NAVD 1988
Single family residence is to have lowest finished floor elevated at or above the Regulatory Flood Elevation (RFE) and lowest point of any attached appliances is to be at or above the Regulatory Flood Elevation (RFE).

4) Floodplain Approval of elevation certificate, prepared by an Arizona State Registered Land Surveyor, is required prior to the finished construction or Final Inspection (P2F). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the single family residential structure, shop and studio if applicable, as well as the identity and location of all other equipment/machinery servicing the single family residential structure.

5) Floodplain Approval of elevation certificate, prepared by an Arizona State Registered Land Surveyor, is required prior to the pouring of the slab or intermediate Inspection (P2I). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the single family residential structure, shop and studio if applicable, as well as the identity and location of all other equipment/machinery servicing the single family residential structure.

6) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T17OT00465 FOR INFORMATION PLEASE CALL 791-5550."

7) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval.

8) All work shall conform to the approved site plan, T17CM03451, which is made part of this permit.

9) This permit is specific to the improvements for 3309 E Seneca as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit.


This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit.

APPLICANT NAME: Dennis Cozzetti
ADDRESS: 3849 E Calle De Soto, Tucson Arizona 85716
PHONE: 520-323-7700
CONTRACTOR: TBD
ADDRESS: TBD
PHONE: TBD

(EXPIRATION DATE) Month: 05 Day: 03 Year: 2018

SIGNATURE OF APPLICANT DATE

The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.