Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - FLOODPLAIN
Permit Number - T17OT00187
Review Name: PLANS OK TO SUBMIT - FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2017 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | February 21, 2017 FLOODPLAIN USE PERMIT NO: T17OT00187 ADDRESS: 370 W Michigan Drive Tucson, Arizona 85714 PROPERTY OWNER: Francisco and Amelia Verdugo 364 W Michigan Drive, Tucson Arizona 85714 The use a portion of the FEMA Special Flood Hazard Area Zone AE per the Flood Insurance Rate Maps 04019C2286L, specifically described as: A Portion of Parcel 120-07-5890; National City No 3 Lot 5 EXC N7.5' For Alley BLK 44 For the purpose of constructing/converting an existing structure to a guest house. The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and is particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Unified Development Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit. This floodplain use permit is issued with the following 8 conditions: 1) This permit becomes invalid and is subject to additional floodplain review, if any required development changes the demolishing of the buildings, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from demolishing the commercial building within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson. 2) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties. 3) For purposes of this permit the following flood elevations shall be used for the constructing/converting an existing structure to a guest house: Base Flood Elevation (BFE) = 2454.05 feet NAVD 1988 Regulatory Flood Elevation (RFE) = 2455.05 feet NAVD 1988 Gust House is to have lowest finished floor elevated at or above the Regulatory Flood Elevation (RFE) and lowest point of any attached appliances is to be at or above the Regulatory Flood Elevation (RFE). 4) Floodplain Approval of elevation certificate, prepared by an Arizona State Registered Land Surveyor, is required prior to the finished construction or Final Inspection (P2F). The Elevation Certificate must include the identity and elevation of the lowest service equipment/machinery servicing the guest house, if applicable, as well as the identity and location of all other equipment/machinery servicing the guest house. 5) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T17OT00187 FOR INFORMATION PLEASE CALL 791-5550." 6) Any additional future disturbance of the floodplain shall have separate floodplain use permit applications submitted to this office for review and approval. 7) All work shall conform to the approved site plan, T17CM01364, which is made part of this permit. 8) This permit is specific to the improvements for 370 W Michigan as indicated on the approved plans. It shall not apply to any other structure or property, whether attached or unattached, not specified under this permit. This Floodplain Use Permit will be automatically revoked and becomes invalid if conditions are not complied with, as set forth in this permit. APPLICANT NAME: Luis G Mircles ADDRESS: 6709 S Downing Ave, Tucson, AZ 85756 PHONE: 520-269-0649 CONTRACTOR: Luis Mireles ADDRESS: 3815 E 38th Street, Tucson Arizona 85713 PHONE: TBD (EXPIRATION DATE) Month: 02 Day: 21 Year: 2018 SIGNATURE OF APPLICANT DATE The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions. |