Permit Number: T17OT00086
Parcel: 107083110

Address:
890 W GRANT RD

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T17OT00086
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2017 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Please remove the extraneous material not related to drainage. The contents of appendix B and the discussion of them is not relevant to the drainage concerns. It needs to be clear that approval of the drainage report cannot be construed as approval of the contention that the improvements had approval from the city without permits.
2. Number all pages in the report. Refer to exhibits by page number throughout the discussion.
3. Ensure the exhibits have enough detail and clarity for review. For example, figure 3 is not clear and cannot be confirmed separately. Additional comments may be forthcoming once a legible set of exhibits is provided.
4. Once the site and improvement plans have been designed, this report will need to be revised to account for the drainage structures and other improvements proposed for the site.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2018 BLARSON1 OUT TO CUSTOMER Completed