Permit Number: T17CM09504
Parcel: 14024058G

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM09504
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2018 JVINCEN1 FIRE REVIEW Approved
01/18/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/23/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide full compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for Plan Submittal Requirements. The luminaires shown on plan sheet PV-7.1 are in violation of section 402.1, Light Source Color Temperature.
#2. Ref; Plan Sheet PV-4.0. The grounding electrode conductor for the 150 kva transformer should be 1/0 AWG not 4 AWG. NEC art, 250.30A5, 250.66.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/05/2018 KROBLES1 OUT TO CUSTOMER Completed