Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM09462
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/17/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/24/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S3; Spread Footing Schedule: A footing F2 is listed in this schedule, but no structural calculation was located for this footing. Please verify. 2. Sheet S4; Spread Footing Schedule: The footing in the schedule is marked as F2, while the framing plan indicates F1. Please revise. |
| 01/30/2018 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/30/2018 | KROBLES1 | OUT TO CUSTOMER | Completed |