Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM09459
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/17/2018 MARTIN BROWN FIRE REVIEW Approved
01/24/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S3 (Drilled Pier Schedule); Structural Calculations (Sheet 38): The calculations indicate the required drilled pier depths of 6'-6" (concrete), 10'-10" (unrestrained), and 8'-8" (asphalt), while the schedule indicates 6'-4" (concrete), 10'-6" (unrestrained), and 8'-5" (asphalt). Please coordinate.
2. Sheet S3; Spread Footing Schedule: A footing F2 is listed in this schedule, but no structural calculation was located for this footing. Please verify.
01/30/2018 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2018 KROBLES1 OUT TO CUSTOMER Completed