Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM09459
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
01/24/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S3 (Drilled Pier Schedule); Structural Calculations (Sheet 38): The calculations indicate the required drilled pier depths of 6'-6" (concrete), 10'-10" (unrestrained), and 8'-8" (asphalt), while the schedule indicates 6'-4" (concrete), 10'-6" (unrestrained), and 8'-5" (asphalt). Please coordinate. 2. Sheet S3; Spread Footing Schedule: A footing F2 is listed in this schedule, but no structural calculation was located for this footing. Please verify. |
01/30/2018 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/30/2018 | KROBLES1 | OUT TO CUSTOMER | Completed |