Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM09426
Parcel: 110113610

Address:
2480 N SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM09426
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 9; Sheet A5.1; Detail 02: The epoxy anchor indicates 16" long on the left, but the anchor on the right depicts 6" length. Please verify and indicate the anchor spacing.
2. Previous Comment 10; Sheet A5.1; Detail 07: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the dimensions and elevations.
3. General: Please provide written responses to all review comments.
02/23/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the plumbing design so that all vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Note: see the definition of horizontal pipe. Reference: Sections 202 and 905.4, IPC 2012.
2. Appliances (e.g. pizza oven D823E) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
3. Revise details PSD-7 and PSD-7A to provide separate indirect waste pipes for each compartment of the 3-compartment sinks to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
02/26/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The detail has been renamed Detail HSD-4 on sheet M5.1 but the same comment still applies. [Initial comment: Revise the exhaust duct fire wrap note in detail 2/M0.0 to indicate that a field-applied grease duct enclosure must continuously enclose all sides of the grease duct from the duct origin to the duct termination. Reference: Section 506.3.11.2, IMC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2018 QJONES1 REJECT SHELF Completed