Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM09408
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2019 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Passed | |
| 05/20/2019 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | 1. All building components below the regulatory flood elevation (RFE) must meet the requirements of "Flood Damage-Resistant Materials Requirements" FEMA Technical Bulletin 2, August 2008 or later. Please provide documentation that all materials used below the regulatory flood elevation meet the requirements of the Technical Bulletin. 2. Clearly show on all relevant plan sheets the required flood venting for the enclosure below the RFE. Provide documentation that the flood venting meets the requirements of FEMA Technical Bulletin 1. 3. Show elevation of the gas meter to above the RFE or provide a letter from SWGas certifying its meters are suitable for potentially flooded situations. 4. Show how use of the lowest floor will be restricted to parking and storage. Provide recorded document or other equivalent mechanism to ensure continued compliance with this requirement. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/21/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 05/21/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 05/21/2019 | QJONES1 | REJECT SHELF | Completed |