Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T17CM09404
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. #1. Provide overcuurent protection for the secondary side conductors and panel 'E' as required per NEC art. 408.36B. #2. Provide panel schedules for both panels . Ref: 2012 IBC sec 107.2.1, 2011 NEC |
| 03/14/2018 | QJONES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/14/2018 | QJONES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/14/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 03/14/2018 | QJONES1 | OUT TO CUSTOMER | Completed |