Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM09404
Parcel: 13215003L

Address:
770 E EVANS BL

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T17CM09404
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment.
Also provide a written response.
#1. Provide overcuurent protection for the secondary side conductors and panel 'E' as required per NEC art. 408.36B.
#2. Provide panel schedules for both panels .
Ref: 2012 IBC sec 107.2.1, 2011 NEC
03/14/2018 QJONES1 BUILDING-COMMERCIAL REVIEW Needs Review
03/14/2018 QJONES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2018 QJONES1 APPROVAL SHELF Completed
03/14/2018 QJONES1 OUT TO CUSTOMER Completed