Permit Number: T17CM09404
Parcel: 13215003L

Address:
770 E EVANS BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM09404
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2018 ALEXANDRA HINES ZONING REVIEW Approved
01/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for DHP-1 through DHP-4.
2. Provide efficiency specifications for the rooftop units being installed.
3. Verify the air flow rate specifications for EF-2, EF-3, and EF-4.
4. Provide heating/cooling load calculations for HP-1 and HP-2.
01/08/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a lighting control detail or clarify how the lighting circuits for the 30 and 40 amp circuits are to be distributed along the luminaires.
#2. Panel 'E' panel schedule shows the bus rating at 200 amps and main lugs at 100 amps. Please clarify.
#3. Provide a grounding detail for the new 100 KVA transformer.
#4. Provide power information on the electrical plans for the exhaust fans. Verify that they are rated at 1 HP.
Ref; 2012 IBC section 107.2.1, 2011 NEC
01/08/2018 AHINES2 ENGINEERING REVIEW Passed
01/08/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide metering faucets for the new lavatories that dispense no more than 0.25 gallons per metering cycle. the cycle shall be at least 10-seconds for accessibility.
2. Provide tempered water for the new lavatories using mixing valves that are listed to ASSE 1070. The maximum temperature shall be 110 degrees Fahrenheit.
3. Provide specifications for the proposed water heater.
01/08/2018 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size of the existing water meter and its serial number.
2. What will be the demand served by the water meter?
3. Is there a reduced pressure principle backflow preventer (RP) at the meter? What is its size?
01/10/2018 ARUIZ1 BUILDING-COMMERCIAL REVIEW Needs Review
01/10/2018 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/22/2017 JVINCEN1 FIRE REVIEW Approved