Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM09349
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/20/2017 | KELLY LEE | ZONING | REVIEW | Approved | |
12/20/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Recirculating air from a nail salon to a different occupancy is prohibited. Reference: Section 403.2.1 (3), IMC 2012. 2. The minimum exhaust flow rate from a nail station is 50 CFM. Reference: Table 403.3, IMC 2012. |
12/20/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/20/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
12/20/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/20/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/20/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
12/20/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/20/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/21/2017 | QJONES1 | APPROVAL SHELF | Completed |
12/21/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
12/21/2017 | QJONES1 | REJECT SHELF | Completed |