Permit Number: T17CM09349
Parcel: 13331159W

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM09349
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/20/2017 KELLY LEE ZONING REVIEW Approved
12/20/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Recirculating air from a nail salon to a different occupancy is prohibited. Reference: Section 403.2.1 (3), IMC 2012.
2. The minimum exhaust flow rate from a nail station is 50 CFM. Reference: Table 403.3, IMC 2012.
12/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/20/2017 LOREN MAKUS ENGINEERING REVIEW Passed
12/20/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/20/2017 ROBERT SHERRY WATER REVIEW Completed
12/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/20/2017 MARTIN BROWN FIRE REVIEW Approved
12/20/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2017 QJONES1 APPROVAL SHELF Completed
12/21/2017 QJONES1 OUT TO CUSTOMER Completed
12/21/2017 QJONES1 REJECT SHELF Completed