03/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating cooling load calculations to verify the capacities for the proposed AC units.
2. Provide specifications for the proposed AC units.
3. Show the size, route, and termination point for the condensate drains.
4. Show that the rooms have adequate ventilation per Section 403.3, IMC 2012.