Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM09342
Parcel: 113091670

Address:
2590 N 1ST AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM09342
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating cooling load calculations to verify the capacities for the proposed AC units.
2. Provide specifications for the proposed AC units.
3. Show the size, route, and termination point for the condensate drains.
4. Show that the rooms have adequate ventilation per Section 403.3, IMC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/22/2018 QJONES1 APPROVAL SHELF Completed
03/22/2018 QJONES1 OUT TO CUSTOMER Completed
03/22/2018 QJONES1 REJECT SHELF Completed