Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM09342
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/08/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating cooling load calculations to verify the capacities for the proposed AC units. 2. Provide specifications for the proposed AC units. 3. Show the size, route, and termination point for the condensate drains. 4. Show that the rooms have adequate ventilation per Section 403.3, IMC 2012. |