Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM09342
Parcel: 113091670

Address:
2590 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM09342
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2017 ANDREW CONNOR ZONING REVIEW Approved
12/19/2017 ACONNOR1 ENGINEERING REVIEW Passed
12/20/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
12/20/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/20/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/20/2017 ROBERT SHERRY WATER REVIEW Completed
12/21/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/21/2017 MARTIN BROWN FIRE REVIEW Approved
12/21/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed