Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T17CM09288
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Provide the site utility plan showing the location of the proposed water meter, backflow preventer, and the water service pipe. Specify the size of the proposed water meter and the size of the reduced pressure backflow assembly being installed. Specify the material of construction for the water service pipe. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf 2. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water (i.e. not inside of the building as shown in detail 4/P-4). Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 01/09/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the sequence of operation for the restroom exhaust fan, EF-3, so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012. |
| 01/09/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the civil site utility plans referenced on sheet P-1 that show the material, size, route, and slope of the building sewer and the location of its connection to the public sewer. Reference: Section 107.2.1, IBC 2012. 2. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the cycle time for each metering faucet will last for at least 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 4. Show how the specified water heater will allow the metering faucets for the lavatories to dispense tempered water. Reference: Sections 303.2 and 607.1, IPC 2012. 5. Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012. 6. Verify the horizontal roof area used for calculating the roof drainage requirements. Include the area of the wall caps that drain onto the roof and 50% of the vertical wall areas surrounding the roof when calculating the drainage requirements. Reference: Sections 1106.2 and 1106.4, IPC 2012. 7. Provide structural calculations to show that the roof is capable of supporting 6" of water ponding (4" of head plus 2" to the bottom of the secondary scuppers). Reference: Section 1108.3, IPC 2012. 8. Coordinate the vertical opening dimensions of the scuppers as shown in details 5/A3, 6/A3 and the drainage calculations in roof plan 1/A3. Reference: Section 107.2.1, IBC 2012. |
| 01/10/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet T1. The drawing index for electrical lists plan E1 through E7. Could not locate plan E7 in the plan set. #2. Ref; Plan Sheet E5. Provide a fault current analysis and show the fault current ratings of the service equipment and justify the fault current ratings of the load centers. #3. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code as outlined in section 104 of the Code. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. Ref: 2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code. |
| 01/17/2018 | DAVID RIVERA | ZONING | REVIEW | Reqs Change | FROM: David Rivera PDSD Zoning Review Section PROJECT: T17CM09288 - Big O Tires Building plans (1st Review) 10061 E Old Vail Road TRANSMITTAL DATE: January 17, 2018 DUE DATE: January 18, 2018 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. The proposed modifications to the interior do not affect any zoning requirements and the use of the building and site is not changing. 2. COMMENT: In addition, the building plans must be approved by the PDSD commercial plans reviewers before zoning can approve the plans. 3. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and no site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview. If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov |
| 01/23/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/21/2017 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Conflicting information on Code Data and Deferred Submittal notes. Deferred Submittal information states sprinklers and alarms will be deferred, Code Data states it is not sprinklered. Please clarify. |
| 12/28/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet T1; Code Data (Applicable Codes): The IBC, IPC, IMC, IECC, IFGC, and IFC indicate the 2015 Edition was used for this project. The 2012 Edition is the current adopted code for the City of Tucson. An appeal must be made to the building official to use the 2015 Edition of those codes in place of the 2012. If you want to request using the 2015 codes, please submit the form from the City of Tucson website (www.tucsonaz.gov/PDSD). 2. Sheet A1 (Floor Plan); Sheet A8.2 (Elevations 2 and 3): Are these elevations correct per the floor plan? Please verify. 3. Sheet A1.1; Door Schedule: Door 102 should be a double door. Please verify. 4. Sheet A1.3; Fixtures and Furniture Plan: In the Waiting Area (#102), the counter top (Tag 55) and the coffee maker/water dispenser (Tag 73) must be accessible per the ICC/ANSI Section 902. Please add a remark on the Fixtures Schedule indicating those specific requirements. 5. Sheet A1.3; Fixture and Furniture Plan: In the Lounge Area (#105), the counter must be accessible per the ICC/ANSI Section 902. Please add a remark on the Fixtures Schedule indicating those specific requirements. 6. Sheet A1.3; Fixture and Furniture Plan: In the Sales Area (#101), the sales counter (Tag 53) is noted in the Fixture Schedule as accessible. Please add a remark in the Fixture Schedule indicating the specific requirement for this counter per the ICC/ANSI Section 904. 7. Sheet A4; Elevation 2: Sections 1/A5 and 2/A5 are cut on this elevation. The sections indicate the roof joists bearing on the exterior wall. At this wall, the roof joists are parallel to the exterior wall. Please verify. 8. Sheet A4; Elevation 3: Sections 1/A5, 3/A5, and 4/A5 are cut on this elevation. The sections indicate the roof joists bearing on the exterior wall. At this wall, the roof joists are parallel to the exterior wall. Please verify. 9. Sheet A5 (Wall Section 4); Sheet A9 (Section 7): Section 7 indicates the "Bottom of the canopy see wall section-Sheet A5". However, Wall Section 4/A5 does not indicate that information. Please provide. 10. Sheet A7; Restroom Elevations 2B and 3B: Please provide the vertical grab bar per the ICC/ANSI Figure 604.5.1. 11. Sheet A9; Cabinetry Details 2, 3, and 4: Please darken the text. 12. Sheets A10.1 through A10.10: Please darken the text. 13. General (Architectural): The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in actual height. Please revise all sheets as required. 14. Sheet S1.1; General Notes: Note 1 indicates the 2009 Edition of the IBC was used. Please revise that note to the 2012 Edition, and verify all design meets the requirements of that code. 15. Sheet S1.1; Soil Preparation Notes: Note 1 indicates the 2009 Edition of the IBC was used. Please revise that note to the 2012 Edition, and verify all design meets the requirements of that code. 16. Sheet S1.1; Soil Preparation Notes: Note 1 uses an assumed allowable bearing capacity and allowable lateral capacity. An actual geotechnical evaluation was provided, and should be noted on the drawings. 17. Sheet S1.1; General Notes: Many code sections and table references were found on this sheet that are no longer valid in the 2012 IBC. Please revise those references. 18. Sheet S2.1; Foundation Plan: The two smaller lift pits do not indicate the floor elevation changes (see the large lift pit). Please provide. 19. Sheet S2.1; Foundation Plan: Please add a note at the three lift pits to reference the architectural sheets for size and location. 20. Sheet S2.2; Roof Framing Plan: Please add a note at the roof opening indicated over the Tire Storage Area to reference the mechanical sheets for the heat and smoke vent size and location. 21. Sheet S2.2; Roof Framing Plan: Please add a note at the Roof Hatch Opening to reference the architectural sheets for the size and location. 22. Sheet S3.1; Sections 01, 02, 04, 05, 08, and 09: These sections indicate to see the plan for the top of footing elevation. This elevation was not located on any plan. Please verify. 23. General (Structural): The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in actual height. Please revise all sheets as required. 24. General (Structural): Please provide two sets of sealed, signed, and dated structural calculations. 25. General (Structural): Per the Rules of the Arizona State Board of Technical Regulation, Section R4-30-304, the registrant shall include a notation beneath the seal that provides the day, month, and year of the expiration of the current registration. Please provide on the structural calculations and drawings. 26. General: More comments may be added during subsequent reviews due to the incomplete submittal documents. 27. General: Please provide written responses to all review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/09/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 02/09/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 02/09/2018 | QJONES1 | REJECT SHELF | Completed |