Permit Number: T17CM09258
Parcel: 127035510

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM09258
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approved
02/14/2018 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved
02/14/2018 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Approved
02/15/2018 DAVID RIVERA ZONING REVIEW Approved
02/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed by the architect. [Second comment: Provide specifications for the kitchen appliances.] [Initial comment: Provide specifications for the kitchen appliances and plumbing fixtures. Verify the number of ranges in the kitchen; the drawings show two ranges. Reference: Section 107.2.1, IBC 2012.]
2. Comment not addressed by the architect. [Second comment: Comment not addressed.] [Initial comment: Verify that the discharge from the dishwasher will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.]