Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T17CM09237
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2018 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Plans and permits are very confusing. There are references to buildings identified by both letters and numbers on sheet TS. Permit cards have the same problem. Sheet A1.00 only identifies 5 buildings. Unable to locate area calculations. It appears there are a lot of buildings on a fairly small lot. Be advised that if you are using sprinklers to increase building area, sprinklers must be installed to a full NFPA 13 standard. Please indicate in deferred submittal section of sheet TS. Note on sheet TS indicates no sprinklers in building 2. Please verify. |
| 02/01/2018 | STEVE SHIELDS | ZONING | REVIEW | Needs Review | |
| 02/05/2018 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL Sheet 84 Provide GFI notation at require receptacles per section NEC 210.8 Sheet 86 Provide landscape lighting to the Outdoor Lighting Calculation Sheet 87 GFI storage per section NEC 210.8 |
| 02/05/2018 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | PLUMBING – COMMERCIAL Sheet 71 Show connection to sewer. Sheet 71 Should this be p-7? Coordinate Plumbing Fixture ID’s with Plumbing fixture schedule on sheets 71 & 80 Sheet 71 Should this be p-7? Coordinate Plumbing Fixture ID’s with Plumbing fixture schedule on sheets 71 & 80 Sheet 71 Should these be p-6? Coordinate Plumbing Fixture ID’s with Plumbing fixture schedule on sheets 71 & 80 Sheet 80 On partial Waste & Vent Isometric A, should this be p-7? Coordinate Plumbing Fixture ID’s with Plumbing fixture schedule on sheets 71 & 80 Sheet 81 These fixtures do not appear to be connected to the grease interceptor on the plumbing plan and isometric. Revise gi sizing calculation. Sheet 81 2012 IPC table e103.3(3) indicates a demand of approximately 49.2 GPM for 133.2 WFU. Please explain. Sheet 81 The civil utilities drawing identifies a 2" RPBP and water service line rather than a 3" RPBP. 2012 IPC figure e103.3(3) would seem to support this for 75 GPM demand; although at 49.2 GPM a 1 1/2" RPBP and service line seems to be ok as well. Please review. Sheet 81 this fixture does not seem to appear on the plumbing plan or axonometric DWGS |
| 02/05/2018 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T17CM09232, T17CM09233, T17CM09234, T17CM09235, T17CM09236, T17CM09237 – PLAN REVIEW COMMENTS Reviewer: Larry Chavez, Building; Chris Anderson, Mechanical; Charlie Bard, Electrical- January 26, 2018 BUILDING – COMMERCIAL Sheet 1 On the Occupant Load – Public Building, occupant load for a space shall be based on the function of the space (even though the occupancy may be classified as a group b (303.1.2) conference room OLF is 1/15 sf or per furniture layout. Sheet 1 Under Fire Separation Distance + Assemblies, complete the IBC 208 reference with the rest of the sentence, “provided that automatic sprinklers are installed in combustible floor/ceiling and roof/ceiling spaces. Sheet 1 Include rest of provision from code, “Provided that automatic sprinklers are installed in combustible floor/ceiling and roof/ceiling spaces.” Sheet 4 How is the roof being accessed? Per IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches. Sheet 18 Table 602-- Where the fire separate distance is 30' or greater, the fire-resistance rating requirement for exterior walls is 0 hours. The fire-resistance rating for less than 30' is 1 hour. Sheet 19 Wherever wall types area cited, call out fire rated assemblies by IBC item number (table 721.1(2)) or UL listing or other similar agency rating. Sheet 21 Show & state compliance with 1107.6.1 Group R-1. Accessible units and Type B units shall be provided in Group R-1 occupancies in accordance with Sections 1107.6.1.1 and 1107.6.1.2. Sheet 21 Wherever wall types area cited, call out fire rated assemblies by IBC Item Number (Table 721.1(2)) or UL listing or other similar agency rating. Sheet 21 Show and state compliance with A1109.1: Accessible units, Type A units and Type B units shall comply with Chapter 10 of ICC A117.1 Sheet 21 State R-value for exterior envelope per 2012 IECC Table C402.2 & envelope requirements per C402.3 for windows & doors Sheet 39 Wherever horizontal fire rated assemblies are required, call out by IBC Item Number (Table 721.1(3)), UL listing or other similar testing agenc |
| 02/05/2018 | FRODRIG2 | WATER | REVIEW | Denied | |
| 02/05/2018 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | MECHANICAL – COMMERCIAL Sheet 4 (Copy from above) How is the roof being accessed? Per IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches Sheet 68 Grease duct to be designed and installed to provide an air velocity of not less than 500 fpm. 2012 IMC 506.3.4. Sheet 69 Per 2012 IMC 507.2.1 type I hood exhaust fan shall also be interlocked with cooking appliances that produce grease or smoke. Sheet 69 OA requirement for bedrooms is not met in heat pump schedule. Sheet 69 The outdoor design DB temperature for summer is 104-degrees f per cot amendment to the 2012 IECC. Please explain how the selected equipment is in compliance with this amendment. Sheet 69 The outdoor summer design temperature used to calculate cooling loads range from 96.2 - 110 degrees f. The ASHRAE summer design DB temperature for Tucson is 104-degrees f per cot amendment to the 2012 IECC. Please explain how your load calculations comply with the cot amendment. Sheet 69 The capacities of the selected cooling equipment appear to be substantially less than the calculated cooling loads. Please explain your logic. |
| 02/08/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Needs Review | Review will be performed at the counter on next submittal. Show the reviewer how roof drainage meets DP requirements for floodfree sidewalks. |
| 02/09/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/27/2018 | ARUIZ1 | OUT TO CUSTOMER | Completed |