Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM09190
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2018 | MGAYOSS1 | ZONING | REVIEW | Approved | |
| 04/10/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide the total water demand that will be served by the meter. Clarify water & fire construction note 1: are you referring to the meter installation? Clarify water and fire construction note 6. It applies only to the fire service but is shown relating to the water service on sheet 2 of 2. [Initial comment: Show the location, size and serial number of the water meter that will serve the building. Show the location and size of the backflow preventer. Provide the total water demand that will be served by the meter. Reference: Section 107.2.5, IBC 2012 and Chapter XXVII, Article V, Section 27-72, the Tucson Code.] |