Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM09185
Parcel: 138244140

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM09185
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM09185 - PLAN REVIEW COMMENTS
BUILDING – COMMERCIAL: reviewer Chris Anderson, January 3, 2018
The exterior walls insulation values shown in the ‘R’ and ‘U’ Values chart, sheet TS1, the partition types schedule, sheet A1.0, the envelope COMcheck, and the wall sections, sheet A5.1, do not match. Please revise each so that information is consistent and also add the 1” continuous board insulation specified in the partition types schedule to the COMcheck and ‘R’ and ‘U’ Values chart. Be aware that “7.5 R-value required” in the ‘R’ and ‘U’ Values Chart is not the minimum prescriptive insulation required by the 2012 IECC Table C402.2 for climate zone 2.
Revise specification section DIV 7 THERMAL MOISTURE PROTECTION section B(2)(b)(2) so that the exterior wall insulation R-value matches the revised envelope COMcheck , partition schedule, and wall sections as discussed in building comment 1 above. Ref. 2012 IBC 107.2.1.
Since this building has been classified as “separated” uses in the “Code Analysis Data”, sheet TS1, make the following changes to notation on the code plan, sheet G1.0, as follows: a) change the occupancy group for “Processing” from M-mercantile to S-1 - storage, b) add “(accessory occupancy)” after “M-mercantile” for Job Training, Job Connection, and Break Room, and c) change M-mercantile to B-business for the “Office.” Ref. 2012 IBC 303.1.2 and 508.4.1.
The Janitor, Break Room, Office and Processing portion of the building requires two exits as the total occupant load is greater than 29. Ref. 2012 IBC Table 1015.1.
Add a boxed note to the right of the Door Frame Types schedule on sheet A6.0 that clearly identifies the U-factors for exterior doors (glazed, non-glazed and roll-up) and windows as shown in the building envelope COMcheck. Also note that the maximum SHGC for windows and glazed doors shall be 0.25. As an alternative to this note, add this information in the product specifications, sheets SP1-SP2. Ref. 2012 IBC 107.2.1.
The steel column base plate is shown in Column Schedule, sheet S1.5, as 11” x 11” x ½”, while structural calculations, pages 84 and 85, show the required size to be 11” x 11” x 5/8”. Please explain. Ref. 2012 IBC 107.2.1.
The interior column footings shown on sheet S2.0 are called out as “C4.” Presumably they should be labeled “F4.” Ref. 2012 IBC 107.2.1.
The front wall shown in entry detail 212/S5.0 is offset 2” from face of beam. This is not shown on the architectural wall section 1/A5.1. Please explain. Ref. 2012 IBC 107.2.1.
The front wall shown in exterior wall section 1/A5.1 is stepped back just below the roof rafters and parapet; however this is not shown on the entry detail 212/S5.0. Please explain. Ref. 2012 IBC 107.2.1.
01/04/2018 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL: reviewer Charlie Bard, January 3, 2018
Lighting requirements per the outdoor lighting code is 3500k maximum color temperature, See sheet E1.2 and lights SCE,SD,SF, and SFE are all 4000k. Ref. 2012 OLC 402.1.
Provide outdoor Lighting Code lumen calculations per Table 401.1 of the 2012 Pima County/City of Tucson Outdoor Lighting Code to show compliance.
01/04/2018 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL: reviewer Chris Anderson, January 3, 2018
Submit heating and cooling load calculations summary sheets based on summer db outdoor air design temperature of 104-degrees F, design wb temperature of 66-degrees F, and winter design db temperature of 32-degrees F. Ref. City of Tucson amendment to 2012 IECC, new section C302.2.
A remark in the Exhaust Fan Schedule, sheet M2.1, for restroom exhaust fans 1 & 2 calls for the fans to be interlocked with the restroom light switches. Supply air is introduced into each restroom so please explain how negative pressure will be maintained in the restrooms to prevent recirculation of foul air to other spaces. Ref. 2012 IMC 403.2.1.
Total supply air introduced into each restroom from the associated air handler(s) is 200 CFM. However, both exhaust fan 1 and exhaust fan 2 have a capacity of 150 CFM. How will negative pressure be maintained in these rooms? Ref. 2012 IMC 403.2.1.
01/10/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Goodwill @ 1703 W. Valencia Road
T17CM09185
Building Plan (1st Review)

TRANSMITTAL DATE: January 10, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until development package DP17-0273 is approved the building plans cannot be approved.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/10/2018 SSHIELD1 ENGINEERING REVIEW Needs Review
12/14/2017 ROBERT SHERRY WATER REVIEW Completed
12/15/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer. Reference: Sections 104.2 and 107.2.1, IBC 2012.
2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure (no details shown in the architectural or structural drawings). Reference: Section 301.2, IPC 2012.
3. With regard to connection to the existing private sewer collection system, saddle-type fittings are only allowed where the diameter of the common sewer pipe is twice the diameter of the building sewer connecting to the common sewer pipe (e.g. a 4" building sewer connecting to an 8" common sewer). Saddle-type fittings are prohibited for use in sewer systems built under the IPC. Reference: Section 707.1, IPC 2012.
4. Provide the rim elevation of the next upstream sanitary manhole or cleanout. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.
5. Clarify how the width of the scuppers was determined (e.g. flow rate and water head). Reference: Section 107.2.1, IBC 2012.
12/21/2017 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2018 FERNE RODRIGUEZ REJECT SHELF Completed