Permit Number: T17CM09181
Parcel: 11615077K

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM09181
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/13/2017 ALEXANDRA HINES ZONING REVIEW Approved
12/13/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/13/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/13/2017 AHINES2 ENGINEERING REVIEW Passed
12/13/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G2.0; Applicable Codes: The accessibility code should be the 2009 ICC/ANSI A117.1. Please revise.
2. Sheet A4.1; Detail 1: A note indicates to anchor to wall in approved manner. Please provide a specific anchor (size and length). In addition, indicate the construction type of the wall.
12/13/2017 ROBERT SHERRY WATER REVIEW Completed
12/13/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the specifications and listing information for the proposed water heater. Reference: Sections 303.2 and 501.5, IPC 2012 and Section 107.2.1, IBC 2012.
2. Provide an approved anti-siphon device (e.g. vacuum relief valve) for storage-type water heaters located above any fixture outlets. Reference: Section 504.1, IPC 2012.
3. If the specified water heater is not supplied with integral heat traps, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012.
12/13/2017 MARTIN BROWN FIRE REVIEW Approved
12/13/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed