Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T17CM09106
Parcel: 132130830

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM09106
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2017 MCASTRO2 ZONING REVIEW Approved
12/11/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify keynote 1 on the mechanical roof plan. The note calls for new heat pumps to replace the existing heat pumps but the schedule on sheet M-1 shows the existing units being re-used. Additional documentation (e.g. cooling/heating load calculations, energy code compliance calculations, etc.) will be required if new units are to be installed. Reference Section 107.2.1, IBC 2012.
2. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and automatic start-up control (i.e. the thermostat is capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy) and, if the thermostat does not require manual changeover from the heating and cooling modes, it restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
3. Show the size, routing, and termination of the condensate drains for the rooftop heat pumps. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
4. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.
5. Coordinate the scheduled airflow quantities for HP-1 and HP-2 with the CFM values shown on the mechanical floor plan. Reference: Section 107.2.1, IBC 2012.
12/11/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/11/2017 LOREN MAKUS ENGINEERING REVIEW Passed
12/11/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T17CM09106
1. Sheet A00-00; Symbol Key: Please revise the door tag symbol. The plan on Sheet A01-01 does not match the symbol key.
2. Sheet A01-01; Floor Plan: A note at the water heater references 12/A06-01 for a detail. Please revise the reference.
3. Sheet A06-01; Partition Type 2: This schedule has four walls indicated as fire resistance rated partitions. Do those apply to this project? Please verify.
4. Sheet A06-01; Typical Wall Detail 2B: The partition notation 'C' indicates the partition to the underside of the ceiling. Does this apply to any partitions on this project? Please verify.
5. Sheet A06-02; Door Schedule: Please add a note indicating the IBC Section 1008.1.9.3(2.2) is met. Please indicate this on the drawings.
6. General: The architect of record must date his seal on each sheet, and indicate the date his registration expires.
7. General: Please provide written responses to all review comments.
12/11/2017 ROBERT SHERRY WATER REVIEW Reqs Change Clarify keynote 1 on detail 5/P-1: will a new water meter from Tucson Water be installed to serve this suite or is the note referring to a submeter from the building? Reference: Section 107.2.1, IBC 2012.
12/11/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070 (ASSE 1016 mixing valve noted on P-1 and P-3). Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Correct the label on detail 1/P-1: a Watts N36 is a vacuum relief, not a vacuum breaker. Reference: Section 504.2, IPC 2012.
4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washers). The pressure-absorbing devices shall conform to ASSE 1010; an air chamber is not acceptable. Reference: Section 604.9, IPC 2012.
5. Identify the backflow preventers shown in the above ground piping diagram. Reference: Section 107.2.1, IBC 2012.
12/11/2017 MARTIN BROWN FIRE REVIEW Approved
12/11/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved