Permit Number: T17CM08987
Parcel: 10706046A

Address:
1308 W GLENN ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM08987
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2018 KELLY LEE ZONING REVIEW Approved
01/05/2018 KLEE1 ENGINEERING REVIEW Passed
01/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide compliance with the 2012 IECC for lighting.
01/05/2018 JVINCEN1 FIRE REVIEW Approved
01/09/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change T17CM08987

1. Sheet A1; Wall Type A: Please indicate the top of the wall on this detail and how it ties into the roof structure (for joists parallel or perpendicular).
2. Sheet A1; Reference Plan: Per the IBC Table 2902.1, a high/low drinking fountain or a single-point-of-use water dispenser (directly connected to water line but no drain required) are required for this use. Please provide on the plan.
01/09/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations to verify the capacity of the new heat pump.
2. Provide specifications for the proposed solatubes (e.g. model number, SHGC, and U-value).
3. Provide ventilation calculations for the space.
4. Revise the HVAC design to avoid using the egress corridor as a duct.
5. The restroom exhaust fans shall operate continuously during hours of operation.
01/09/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
3. Provide specifications for the proposed plumbing fixtures.
4. Correct the size of the fixture drain for the water closet (minimum 3").
01/09/2018 ROBERT SHERRY WATER REVIEW Completed
01/09/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed