Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/05/2018 | KELLY LEE | ZONING | REVIEW | Approved | |
01/05/2018 | KLEE1 | ENGINEERING | REVIEW | Passed | |
01/05/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide compliance with the 2012 IECC for lighting. |
01/05/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
01/09/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | T17CM08987 1. Sheet A1; Wall Type A: Please indicate the top of the wall on this detail and how it ties into the roof structure (for joists parallel or perpendicular). 2. Sheet A1; Reference Plan: Per the IBC Table 2902.1, a high/low drinking fountain or a single-point-of-use water dispenser (directly connected to water line but no drain required) are required for this use. Please provide on the plan. |
01/09/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating/cooling load calculations to verify the capacity of the new heat pump. 2. Provide specifications for the proposed solatubes (e.g. model number, SHGC, and U-value). 3. Provide ventilation calculations for the space. 4. Revise the HVAC design to avoid using the egress corridor as a duct. 5. The restroom exhaust fans shall operate continuously during hours of operation. |
01/09/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. 3. Provide specifications for the proposed plumbing fixtures. 4. Correct the size of the fixture drain for the water closet (minimum 3"). |
01/09/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
01/09/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |