Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T17CM08967
Review Name: RESUBMITTAL
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/21/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Show that the new construction complies with the current energy code (residential) |
| 02/21/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/21/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the water pressure available for this address. 2. Include the pressure drop for the RPBP in the water pressure calculations. 3. A flow rate of 22.5 GPM will result in a water velocity of 8.4 FPS in a 1" schedule 40 PVC pipe. 4. Provide the first floor elevation of the new addition and the rim elevation of the next upstream manhole. Evaluate the need for a backwater valve. |