Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/21/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that the new construction complies with the current energy code (residential)
02/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/21/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the water pressure available for this address.
2. Include the pressure drop for the RPBP in the water pressure calculations.
3. A flow rate of 22.5 GPM will result in a water velocity of 8.4 FPS in a 1" schedule 40 PVC pipe.
4. Provide the first floor elevation of the new addition and the rim elevation of the next upstream manhole. Evaluate the need for a backwater valve.