Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CVR; Code Information: Please clear up the verbiage in the "Fire Protection Provided" and the "Structural Engineer" headings. It is not legible.
2. Previous Comment 6; Sheet CVR; Fire Department Requirements: Please include the required smoke alarms per the IBC Section 907.2.10 in this verbiage.
3. Previous Comment 8; Sheet SP-2; Keynote 12: Please revise the note to indicate 2% cross slope and 1:20 (5%) running slope.
4. Previous Comment 11; Sheet A-1; Door Schedule: Per the IBC Table 716.5, there are minimum fire door assembly ratings for doors in 1/2 hour rated partitions. Please revise the door schedule on this sheet to indicate those required ratings on the appropriate doors.
5. General: Please provide written responses to all review comments.