Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM08967
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/15/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet CVR; Code Information: Please clear up the verbiage in the "Fire Protection Provided" and the "Structural Engineer" headings. It is not legible. 2. Previous Comment 6; Sheet CVR; Fire Department Requirements: Please include the required smoke alarms per the IBC Section 907.2.10 in this verbiage. 3. Previous Comment 8; Sheet SP-2; Keynote 12: Please revise the note to indicate 2% cross slope and 1:20 (5%) running slope. 4. Previous Comment 11; Sheet A-1; Door Schedule: Per the IBC Table 716.5, there are minimum fire door assembly ratings for doors in 1/2 hour rated partitions. Please revise the door schedule on this sheet to indicate those required ratings on the appropriate doors. 5. General: Please provide written responses to all review comments. |