Permit Number: T17CM08967
Parcel: 121080600

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM08967
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2018 STEVE SHIELDS ZONING REVIEW Approved
12/07/2017 JVINCEN1 FIRE REVIEW Approved
12/29/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet CVR; Attic Area: This analysis indicates the 2012 IRC was used to determine ventilation requirements. Revise this reference and use the 2012 IBC Section 1203 for ventilation requirements.
2. Sheet CVR; Code Information (Exits): Since the new addition is the only concern for exiting in this permit, please clarify the one exit (as shown on Sheet A-1) meets the code requirements per the IBC Table 1021.2(2). Omit exiting notes concerning the existing structure.
3. Sheet CVR; Code Information (Applicable Codes): Please remove the reference to the 2012 IRC. This is a commercial project.
4. Sheet CVR; Code Information (Applicable Codes): Please revise the reference of the 2011 ICC/ANSI to the 2009 Edition.
5. Sheet CVR; Code Information (Area): Please indicate a calculation for the total allowable area. 7000 x 300% + 7000 = 28,000 SF.
6. Sheet CVR; Code Information (Fire Department Requirements): Per the IBC Section 907.2.10, fire alarm systems and smoke alarms are required. Please indicate this in the Code Information.
7. Sheet CVR; Code Information (Fire Department Requirements): Please indicate on this sheet the automatic sprinkler system must be included in the attic space to meet the requirements of the IBC Section 718.2 (fireblocking) and Sections 718.3.2 and 718.4 (draftstopping).
8. Sheet SP-2; Keynotes: Note 12 indicates the disabled path shall maintain 2% forward (running) slope and cross-slope. Per the ICC/ANSI Section 403.3, the running slope may be 1:20 (5%).
9. Sheet A-1; Floor Plan: Per the IBC Sections 708.1 and 708.3, the walls separating dwelling units and sleeping units, and corridor walls, must have a fire resistance rating per Section 708.3. In the Wall Legend, indicate the required rating, reference a U.L.Listing Number for that assembly, and indicate all components of that assembly. This will include interior walls and the wall between Bedroom #1 and the existing building to the north.
10. Sheet A-1; Wall Legend: The specific wall types (A, B, and C) indicated in the legend do not show up on the plan. Please add to the plan.
11. Sheet A-1; Floor Plan: There is no door schedule that was located in the drawings. Please provide on the drawings, and include the required fire resistance rating of each door (as required) per the IBC Table 716.5.
12. Sheet A-1: Please indicate on the drawings the requirements for penetrations through the fire resistant walls per the IBC Section 714.
13. Sheet A-1: Please indicate on the drawings the requirements for the joint systems through the fire resistant walls per the IBC Section 715.
14. Sheet A-1: Please indicate on the drawings the requirements for ducts and air transfer openings through the fire resistant walls per the IBC Section 717.
15. Sheet A-1; Floor Plan: The IBC Table 2902.1 indicates a drinking fountain and service sink are required. Please indicate on the plan and provide specifications as required.
16. Sheet A-1; Floor Plan: At the west exterior wall of the addition (at a window), please arrange the verbiage so the two notes are legible.
17. Sheet A-4; Building Sections: A note on this sheet indicates Section BB is deleted. The section cut is still indicated on Sheets A-1, A-2, A-7, and A-8. Please clarify.
18. Sheet A-4; Existing North Elevation: A note at the right end of this elevation indicates "3FT DR" and points to a wall and a window. Please revise the note.
19. Sheet A-6; Roll-In Shower: Please indicate the seat and grab bars in the roll-in shower plan per the ICC/ANSI Figures 608.3.2 or 608.3.3. In addition, please revise elevations of the roll-in shower per Figures 608.4.2 or 608.4.3, indicating grab bars and the control/handshower locations.
20. Sheets S-1 and S-2; Foundation/Framing Plans: Section BB/A-4 was indicated on these plans, although Sheet A-4 indicated that section was to be deleted. Please clarify.
21. Sheet S-1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in actual height. Please revise the Shear Wall Schedule.
22. Sheet S-2; Roof Framing Plan: A Detail 5/S-4 is cut through an interior door. The detail indicates an aluminum window sill detail. Please verify.
23. Sheet S-3; Detail 5: Should the footing width be 18" to match Section 1? Please verify.
24. Sheet S-3; Details 1, 3, and 5: A note on these details indicates "Bottom of footing minimum 12" below natural grade or to firm soil as required". Please revise the 12" dimention to 18".
25. Sheet SN-1; Structural Notes (Foundations): Note 1 indicates an assumed 1500 psf soil bearing value with a minimum depth of 12" below the undisturbed ground surface. The City of Tucson requires 18" of minimum depth for that allowable soil bearing value. Please revise the note (sections do indicate 18").
26. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2018 ARUIZ1 OUT TO CUSTOMER Completed