Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM08928
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/26/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete panel schedules. Ref: 2012 IBC sec 107.2.1, 2012 NEC art 408 |
| 02/26/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/26/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 02/26/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Reference Floor Plan: Please provide the dimensions for the shower on the Enlarged Floor Plan 3/A1. 2. Sheet A1; Enlarged Floor Plan 3: Please provide details for the shower per the ICC/ANSI Section 608.2.2, including grab bars, seat, and control/handshower locations. 3. General: Please provide written responses to all review comments. |