Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T17CM08924
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/20/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Please clarify the extent of this revision (12-15-2017). Sheet A1.0 indicates all of the toilets clouded with a Delta 1. Please verify what the clouded toilets indicates. Sheets A1.1 and A1.2 indicate another cloud and Delta 1. Please explain. |
| 12/20/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/20/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Clarify the revisions to the drawing (e.g. mutiple "delta 2" entries,should one of them be a "delta 3"?). Fill out the revision/release date information. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/22/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 12/22/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 12/22/2017 | QJONES1 | REJECT SHELF | Completed |