Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM08816
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/01/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Appliances (e.g. glasswashers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012. 2. Water supply connections to beverage dispensers (e.g. coffee makers) shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012. |
12/01/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
12/05/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/08/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
12/15/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
12/15/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General Sheets; Sheet G0.6: This sheet is not listed on the Sheet G0.1 Drawing Inventory. Please verify. 2. Sheet G2.1; First Level Plan: The exit access travel distance to a corridor is indicated as 297' to one exit door and 208' to another. The IBC Table 1016.2 indicates 200' as the maximum allowable travel distance in a sprinklered I-2 occupancy classification. Please verify. 3. Sheet AD2.1.1: This sheet indicates it is for reference only. No review was provided. 4. Sheet A0.1: This sheet indicates it is for reference only. No review was provided. 5. Sheet A0.2: This sheet indicates it is for reference only. No review was provided. 6. Sheet A0.3: This sheet indicates it is for reference only. No review was provided. 7. Sheet A7.6.0: This sheet indicates it is for reference only. No review was provided. 8. Sheet A8.6.3: This sheet indicates it is for reference only. No review was provided. 9. Sheet A9.0.1: This sheet indicates it is for reference only. No review was provided. 10. Sheet A9.0.2: This sheet indicates it is for reference only. No review was provided. 11. Sheet A9.3.0.1: This sheet indicates it is for reference only. No review was provided. 12. Sheet A9.4.2: This sheet indicates it is for reference only. No review was provided. 13. Sheet A9.5.1; Typical Casework Types: A note to the right of the added casework types indicates "all 300 series wall hung cabinets to have an added shelf for a total of 2 adjustable shelves". There are two types (300 and 300M) that do not have two adjustable shelves. Please clarify. 14. Sheet A9.6.1: This sheet indicates it is for reference only. No review was provided. 15. Sheet A9.6.2: This sheet indicates it is for reference only. No review was provided. 16. Sheet IN1.1.0: This sheet indicates it is for reference only. No review was provided. 17. Sheet G0.6: Should Sheets G0.5 and G0.6 be inserted to the Sheet G0.1 Drawing Inventory? Please verify. 18. General: Please provide written responses to all review comments. |
12/21/2017 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
12/21/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following Electrical plan review comments. Also provide a written response. #1. Ref: Plan Sheet E3.1.1. The Keynotes #2 and #3 refer to detail 2/E7.0.1 for lighting controls. Could not locate plan sheet E7.0.1. #2. Provide revised interior lighting calcs for the additional lighting. Verify IECC compliance. Ref; 2012 IBC 107.2.1, 2012 IECC, 2011 NEC. |
12/22/2017 | FRODRIG2 | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: Banner - Inpatient Pharmacy T17CM08816 Building Plan (1st Review) TRANSMITTAL DATE: December 21, 2017 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/16/2018 | TWEIDEM1 | APPROVAL SHELF | Completed |
01/16/2018 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
01/16/2018 | TWEIDEM1 | REJECT SHELF | Completed |