Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T17CM08808
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/11/2017 | ROBERT SHERRY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Provide structural calculations to verify the attachment of the proposed antennas. Reference: Section 107.2.1, IBC 2012. |
12/13/2017 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved | LETTER SENT TO RECORDS |
12/27/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please correct the electrical code reference on the Title sheet 'T1'. The current applicable electrical code is 2011 NEC. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/12/2018 | QJONES1 | APPROVAL SHELF | Completed |
01/12/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
01/12/2018 | QJONES1 | REJECT SHELF | Completed |