Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW - COMMERCIAL TI
Permit Number - T17CM08778
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2018 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Approved | |
| 04/11/2018 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/04/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/06/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 12/21/2017 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 12/21/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/12/2018 | BLARSON1 | OUT TO CUSTOMER | Completed |