Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T17CM08700
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/22/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/22/2017 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 11/22/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/22/2017 | QJONES1 | COMMUNICATIONS | REVIEW | Needs Review | |
| 11/22/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/22/2017 | QJONES1 | ZONING | REVIEW | Needs Review | |
| 11/22/2017 | QJONES1 | PLANNING-CITY HALL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/22/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 11/22/2017 | QJONES1 | REJECT SHELF | Completed |
| 11/22/2017 | QJONES1 | APPROVAL SHELF | Completed |