Permit Number: T17CM08699
Parcel: 12009317B

Address:
4625 S 3RD AV

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T17CM08699
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T-1; Sheet Index: Please include the electrical sheet E-1 in the Index.
2. Sheet C-2; Enlarged Site Plan: Please provide a structural calculation indicating the pre-fabricated concrete guy wire blocks (5127 pounds each) and the connection of the guy wires to those blocks are adequate to resist all combinations of applied loads per the IBC Chapter 16.
3. General: Please provide written responses to all review comments.
02/14/2018 KROBLES1 COMMUNICATIONS REVIEW Needs Review
02/14/2018 KROBLES1 PLANNING-CITY HALL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/14/2018 KROBLES1 OUT TO CUSTOMER Completed