| 11/22/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a wiring diagram showing the feeder sizes and types for the generator connections. Include a grounding detail. Ref; 2012 IBC 107.2.1, 2011 NEC |