Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM08666
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/05/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Reconcile the installation detail for the water heater with the architect - details 4/A4.0 and 1/P2.0 are different. Reference: Section 107.2.1, IBC 2012. |
12/05/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Explain the "Storefront Window Energy Spec's" notes on sheet A1.0. The center section of the storefront is being changed from one 3'-0" door to two 3'-0" doors but the U-factor used with the shell construction was 0.350, not "a minimum of 0.5". If the U-factor is to be changed from 0.350, provide a new Envelope Compliance Certificate. (Note: your note should call out the maximum allowable U-factor and SHGC, not the minimum values.) Reference: Section C103.2, IECC 2012. 2. Correct the outdoor air calculation table to show an entry for HP-3. Reference: section 107.2.1, IBC 2012. |
12/18/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.0; Floor Plan: Please provide the symbol next to the "Lead Lining Requirements" that indicates those walls in the X-Ray room. 2. Sheet A1.0; Wall Types: For each new wall type, please reference the specific wall detail shown on this sheet (Detail 1 or 2). Add new wall details as required. 3. Sheet A1.0; Wall Types: On the plan, please indicate the specific wall type for all new interior walls. 4. Sheet A1.1; Means of Egress Width Calculation: A note references IBC Sections 1008.1.8 and 1008.1.8.3 for a required exit door sign. Please revise the references. 5. Sheet A3.0; Door Notes: Note 2 references the ANSI 1008.1.9 for door hardware. Please revise the reference. 6. Sheet A4.0; Detail 4: Please provide the horizontal angle size at the water heater support rack, and include the anchor to wall size. Please indicate the number of frames at the water heater. 7. Sheet A4.0; Detail 4: A continuous blocking note references Detail 2A/A1.0. Please revise the reference. 8. Sheet A4.0; Enlarged Restroom Plan 3: Per the IBC Section 1109.2(1.3), grab bars are not required to be installed in toilet rooms not for common or public use. However, reinforcement must be installed in the walls to permit the installation of such grab bars. Please indicate with a note on this plan and on the wall elevations that this requirement must be met on this permit. 9. General: Please provide written responses to all review comments. |
12/22/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |