Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T17CM08657
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/21/2019 | PIMA COUNTY | BUILDING-COMMERCIAL | REVIEW | Completed | |
02/21/2019 | PIMA COUNTY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/21/2019 | PIMA COUNTY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | ELECTRICAL – COMMERCIAL The site plan has changed significantly from the original permitted site plan. Submit outdoor lighting calculations per the 2012 City of Tucson/Pima County Outdoor Lighting Code Table 401.1. The photometric site plan on sheet E1.2 is not in a form that compliance with this Code can be analyzed. First, add a fixture schedule on sheet E1.2 for all exterior light fixtures. Indicate in the schedule the lumens each fixture produces and show that no fixture has a color temperature more than 3,500K (OLC 402.1). Then, select a commercial lighting option from Table 401.1 for lighting area E3 and provide calculations in tabular form for allowable total lumens (fully shielded plus unshielded) and for the maximum allowable unshielded lumens portion of the total. The proposed total lumens and the proposed unshielded fixtures lumens shall match or be less than the allowable lumens. For each fixture indicate “fully shielded” or “unshielded”. Refer to the definitions for each in the OLC. The photometric site plan on sheet E0.03 does not provide the information required. Omit sheets E2.2 and E3.2 from the drawing set. These plans refer to the warehouse building that was removed from the drawing set as part of this revision. The warehouse is under a separate building permit. Remove panel “L1D” from sheet E4.1. This panel refers to the warehouse building that was removed from the drawing set as part of this revision. The warehouse is under a separate building permit. Modify the HVAC Electrical Schedule and Lighting Fixture Schedule on sheet E4.2 to eliminate fixtures that pertain to the warehouse. The warehouse is under a separate building permit. |
02/21/2019 | KROBLES1 | WATER | REVIEW | Completed | |
02/21/2019 | PIMA COUNTY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Reviewer: Chris Anderson, February 15, 2019 MECHANICAL – COMMERCIAL For the Split System Heat Pump Schedule on sheet M0.2, delete remark 7 in the Remarks column and add remark 9. Tucson is in climate zone 2B. An economizer is required. Ref. City of Tucson amendment R302.2 to the 2012 IECC and 2012 IECC Table C403.3.1(1). Remove EF-2 and EF-3 from the Exhaust Fan Schedule on sheet M0.2. These fans pertain to the warehouse building that was removed from the drawing set as part of this revision. The warehouse is under a separate building permit. Remove UH-2 and UH-3 from the Electric Unit Heater Schedule on sheet M0.2. These heaters pertain to the warehouse building that was removed from the drawing set as part of this revision. The warehouse is under a separate building permit. On the mechanical plan, sheet M1.1, the outside air (keynote 3) duct should be routed to the economizer louver. Ref. 2012 IECC C403.3.1.1.1. Omit sheet M1.2 from the drawing set. This plan refers to the warehouse building that was removed from the drawing set as part of this revision. The warehouse is under a separate building permit. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/12/2019 | KROBLES1 | OUT TO CUSTOMER | Approved |