Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM08579
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed; the three zone valve boxes are located in an area locked off with a card reader for security. [Initial comment: MG2.2.4: How does the location of the three zone valve boxes (ZVB-2-23, ZVB-2-31 and ZVB-2-32) comply with Section 5.1.4.6.7, NFPA 99-2015?] |