Permit Number: T17CM08579
Parcel: 12310001A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM08579
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2018 STANTEC BUILDING-COMMERCIAL REVIEW Approved
01/08/2018 STANTEC ELECTRICAL-COMMERCIAL REVIEW Approved
11/16/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. MG2.2.4: How does the location of the three zone valve boxes (ZVB-2-23, ZVB-2-31 and ZVB-2-32) comply with Section 5.1.4.6.7, NFPA 99-2015?
2. P2.2.2: Verify that the 1" DCW supply to the safety shower complies with the manufacturer's installation instructions. Reference: sections 303.2 and 411.1, IPC 2012.
3. P2.2.4: Cloud the location where the DCW & DHW were removed. Reference: Section 107.2.1, IBC 2012.
4. P3.2.4: Cloud the location where the piping has been removed from the MRI Alcove sink. Reference: Section 107.2.1, IBC 2012.
5. P3.2.4: Cloud the location where the vent has been to the Neptune Docking Station. Reference: Section 107.2.1, IBC 2012.
11/16/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
11/28/2017 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/08/2018 TWEIDEM1 APPROVAL SHELF Completed
01/08/2018 TWEIDEM1 OUT TO CUSTOMER Completed
01/08/2018 TWEIDEM1 REJECT SHELF Completed