Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM08579
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/08/2018 | STANTEC | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/08/2018 | STANTEC | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/16/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. MG2.2.4: How does the location of the three zone valve boxes (ZVB-2-23, ZVB-2-31 and ZVB-2-32) comply with Section 5.1.4.6.7, NFPA 99-2015? 2. P2.2.2: Verify that the 1" DCW supply to the safety shower complies with the manufacturer's installation instructions. Reference: sections 303.2 and 411.1, IPC 2012. 3. P2.2.4: Cloud the location where the DCW & DHW were removed. Reference: Section 107.2.1, IBC 2012. 4. P3.2.4: Cloud the location where the piping has been removed from the MRI Alcove sink. Reference: Section 107.2.1, IBC 2012. 5. P3.2.4: Cloud the location where the vent has been to the Neptune Docking Station. Reference: Section 107.2.1, IBC 2012. |
11/16/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
11/28/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/08/2018 | TWEIDEM1 | APPROVAL SHELF | Completed |
01/08/2018 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
01/08/2018 | TWEIDEM1 | REJECT SHELF | Completed |