Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/02/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The door to the area in which ZVB-2-23 and ZVB-2-32 are located has a card reader. The zone valve boxes should not be in a locked area. [Initial comment: MG2.2.4: How does the location of the two zone valve boxes (ZVB-2-23 and ZVB-2-31) comply with Section 5.1.4.6.7, NFPA 99-2015?]
02/02/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. As per the previous plan review comment #1,"Could not locate a panel schedule for panel '4IAAH-S2". The response stated ,"See sheet E9.4.6 for swbd schedule 4IAAh-S2". The reviewer could not locate the panel as stated.
Ref: 2012 IBC sec. 107.2.1.