Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM08572
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/02/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The door to the area in which ZVB-2-23 and ZVB-2-32 are located has a card reader. The zone valve boxes should not be in a locked area. [Initial comment: MG2.2.4: How does the location of the two zone valve boxes (ZVB-2-23 and ZVB-2-31) comply with Section 5.1.4.6.7, NFPA 99-2015?] |
| 02/02/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. As per the previous plan review comment #1,"Could not locate a panel schedule for panel '4IAAH-S2". The response stated ,"See sheet E9.4.6 for swbd schedule 4IAAh-S2". The reviewer could not locate the panel as stated. Ref: 2012 IBC sec. 107.2.1. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/08/2018 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 02/08/2018 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 02/08/2018 | TWEIDEM1 | REJECT SHELF | Completed |