Permit Number: T17CM08559
Parcel: 11711096D

Address:
100 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM08559
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2017 KELLY LEE ZONING REVIEW Approved
11/16/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify why the duct penetrations of the existing shaft are not equipped with fire dampers.
11/16/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/16/2017 KLEE1 ENGINEERING REVIEW Passed
11/16/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet M102; Floor Plan: Please verify the mechanical room that contains the new unit is fire resistance rated per the 2012 IBC. In addition, new openings through the existing partition walls (for ductwork) must be caulked as required. Please indicate this information on the drawings.
11/16/2017 ROBERT SHERRY WATER REVIEW Completed
11/16/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/16/2017 MARTIN BROWN FIRE REVIEW Approved
11/16/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed