Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM08558
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/16/2017 | KELLY LEE | ZONING | REVIEW | Approved | |
11/16/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide signage stating the developed length of the dryer vent. Reference: Section 504.6.5, IMC 2012. |
11/16/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/16/2017 | KLEE1 | ENGINEERING | REVIEW | Passed | |
11/16/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/16/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
11/16/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The developed length of the hot water supply to the new janitor's sink and to the new clothes washer appears to be greater than 50-feet. Reference: Section 607.2, IPC 2012. 2. Provide water hammer arrestors for the clothes washer. Refreence: Section 604.9, IPC 2012. |
11/16/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/16/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |