Permit Number: T17CM08558
Parcel: 11711096D

Address:
100 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM08558
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2017 KELLY LEE ZONING REVIEW Approved
11/16/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide signage stating the developed length of the dryer vent. Reference: Section 504.6.5, IMC 2012.
11/16/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/16/2017 KLEE1 ENGINEERING REVIEW Passed
11/16/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/16/2017 ROBERT SHERRY WATER REVIEW Completed
11/16/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The developed length of the hot water supply to the new janitor's sink and to the new clothes washer appears to be greater than 50-feet. Reference: Section 607.2, IPC 2012.
2. Provide water hammer arrestors for the clothes washer. Refreence: Section 604.9, IPC 2012.
11/16/2017 MARTIN BROWN FIRE REVIEW Approved
11/16/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2017 QJONES1 APPROVAL SHELF Completed
11/20/2017 QJONES1 OUT TO CUSTOMER Completed
11/20/2017 QJONES1 REJECT SHELF Completed