Permit Number: T17CM08522
Parcel: 12414115B

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM08522
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/11/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 14; Sheet S0; Fastener Schedule: Please remove the Fastener Schedule R602.3(1) from the drawings, and add the IBC Table 2304.9.1 in its place.
2. Previous Comment 19; Structural Calculations; Sheet S0: The structural calculations denote the roof LL as 16 PSF, but the drawings indicate 17 PSF. Please revise.
3. Previous Comment 20; Structural Calculations; Sheet S0: The structural calculations denote the roof DL as 17 PSF, but the drawings indicate 16 PSF. Please revise.
4. General: Please provide written responses to all review comments.
12/19/2017 QJONES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2017 QJONES1 APPROVAL SHELF Completed
12/19/2017 QJONES1 OUT TO CUSTOMER Completed
12/19/2017 QJONES1 REJECT SHELF Completed