Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM08485
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/04/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the water meter serving this building; Tucson Water limits the use of a ¾" water meter to a maximum demand of 22.5 GPM. Provide the size and serial number of the water meter. Reference: Section 107.2.1, IBC 2012. 2. Verify the presence of a reduced pressure backflow prevention assembly for the water service to the building. If present, provide the size and model of the assembly; if not present, show the size, model, and proposed location of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 04/04/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Sun Engineering does not appear to be licensed to provide engineering services in Arizona. 2. Provide economizers for the split systems or increase the SER to 14.3 or greater. 3. Revise the mechanical design as required to avoid using the egress corridors as return air ducts. Reference: Section 601.2, IMC 2012. |
| 04/04/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Correct plumbing calculations |
| 04/13/2018 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |