Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T17CM08399
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 11/13/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 11/13/2017 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 11/13/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/13/2017 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 11/14/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/15/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Lamp color temperature output for the exterior lighting not to exceed 3500 K . OLC sec 402.1 #2. Balance panel loads to within 20%. #3. Provide load calcs for both panels. #4. Correlate panel ampacity and phase ratings with the one line diagram. Ref; 2012 IBC sec 107.2.1, 2011 NEC |
| 11/15/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/15/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/16/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |