Permit Number: T17CM08329
Parcel: 123071850

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T17CM08329
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2018 ARUIZ1 ENGINEERING REVIEW Needs Review
02/16/2018 ARUIZ1 BUILDING-RESIDENTIAL REVIEW Needs Review
11/07/2017 ANDREW CONNOR ZONING REVIEW Reqs Change FROM: Andrew Connor, Planner


PROJECT:
T17CM08329
2416 E. Mabel St.
Garage Conversion -Detached


TRANSMITTAL: 11/07/17


COMMENTS: The following comments are for the purpose of applying for a variance before the Board of Adjustment (UDC Section 3.10.1).


This site is located in the R-1 zone (UDC 4.7.9). Multi-family residential is a permitted use in this zone (Table 4.8-2). ). See Use Specific Standards 4.9.7.B.6, .9 & .10.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The applicant is proposing a detached garage conversion into dwelling unit. The existing set back is 0' setback from the South and the East property lines. The height of the parapet walls are 9' 9" the required setback would be 6' 5".

Board of Adjustment is required for 0' setbacks for habitable space.
11/07/2017 ANDREW CONNOR NPPO REVIEW Passed