Permit Number: T17CM08309
Parcel: 130140370

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM08309
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: Per the IBC Section 107.3.4.1, documents for deferred submittals shall be submitted to the registered design professional in responsible charge who shall review the submittal and forward them to the building official with a notation on the submittal drawings indicating that the deferred submittal documents have been reviewed and found to be in general conformance to the design of the building. Please have the project engineer of record review and stamp the drawings and calculations (with the notation indicated above) before returning them to the City of Tucson for review. This review can be completed over the counter between the hours of 8:00 to 9:30 each morning at the Planning and Development Services Department.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2018 LPEREZ2 OUT TO CUSTOMER Completed