| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. General: Per the IBC Section 107.3.4.1, documents for deferred submittals shall be submitted to the registered design professional in responsible charge who shall review the submittal and forward them to the building official with a notation on the submittal drawings indicating that the deferred submittal documents have been reviewed and found to be in general conformance to the design of the building. Please have the project engineer of record review and stamp the drawings and calculations (with the notation indicated above) before returning them to the City of Tucson for review. This review can be completed over the counter between the hours of 8:00 to 9:30 each morning at the Planning and Development Services Department. |