Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM08309
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/17/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The roof framing drawing, S2.2, still does not include heat pump HP-1 and its 750-pound point load. [Initial comment: The roof framing drawing, S2.2, does not include heat pump HP-1 and its 750-pound point load. Coordinate with the architect. Reference: Section 302.1, IMC 2012.] |
| 01/17/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/18/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The submitted shop drawings from Sonny's for the tunnel equipment call for the plumbing contractor to install a reduced pressure principle backflow prevention assembly (RP) prior to the equipment water supply (see P.14). Show the location for the RP on the plumbing drawings. [Initial comment: Show that each equipment water connection is protected from backflow. Reference Sections 608.1 and 608.16, IPC 2012.] 2. The dry vent for the combination waste and vent system in the equipment room includes a horizontal vent section located between the 4" floor cleanout and the vertical rise of the dry vent (see P2.1). This horizontal section of vent could be blocked by waste flow; relocate the floor cleanout so that this section of pipe may be cleaned if needed. [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] 3. Relocate the backwater valve to provide protection for the drinking fountain. The drinking fountain is installed on a floor that requires the installation of a backwater valve. [Initial comment: The rim elevation of the next upstream sanitary manhole (MH 5831-30, 2524.0') is less than 12" below the first floor elevation of the equipment area and occupied area (2524.19') and is higher than the floor elevation of the wash tunnel (2523.69'). Provide a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson.] 4. The vent for the sand/oil interceptor is located on the wrong side of the interceptor. Reference: Section 103.9, IPC 2012. |
| 01/30/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref: Outdoor Lighting. (a) It was requested to provide full compliance with the Tucson/Pima County Outdoor Lighting Code. The response and Outdoor Lighting calcs are incomplete. As well as lighting area, (E3) , also include option used from table 401.1. (b) The 'SE' exterior luminaires shown on plan sheet E1.0 will also have to be included in the calcs. Provide the type of shielding and color output temperature for these luminaires to verify compliance. See section 402.1. #2. The updated Comcheck for interior lighting could not be located in the plan documents. Ref; 2012 IBC 107.2.1, 2012 IECC, Outdoor Lighting code, 2011 NEC. Dan.santacruz@tucsonaz.gov |
| 02/05/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: Cleanfreak Alvernon Carwash - Building Plans T17CM08309 Building Plan (2nd Review) TRANSMITTAL DATE: February 5, 2018 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The development package sheets provided in the building set either need to be the approved and signed plans, marked as "FOR REFERENCE ONLY" or removed from the building set. 3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 02/14/2018 | JVWINKL1 | ENGINEERING | REVIEW | Reqs Change | 1: Engineering Seal on Civil Sheets is expired, update accordingly 2: Scupper main roof drains through sidewalk. Clearly show how this will be accomplished John Van Winkle john.van-winkle@tucsonaz.gov 520-837-5007 |